Home
EMI/RFI FILTERS
Products
About Us
Blog
FAQs
Resources
Terms and Conditions
Warranty Information
Installation Instructions
Contact Us
PF125S-40-10
1PH COMMERCIAL/INDUSTRIAL FILTER
SINGLE STAGE / CHASSIS MOUNT
SPECIFICATIONS
Max voltage: 0-300VAC
Max current: 40A/Line
Usable frequency: 50/60/400HZ
Operating temp.: -40 To 50C
Leakage current (250V/60HZ): <1mA
Typ. weight, LB(Kg): 0.8(0.36)
Climatic class: 25/100/21
Designed and manufactured in accordance with the following standards:
EN60939-3
CSA22.2 NO. 8
LV Directive
DOWNLOAD SHEET
TYPICAL INSERTION LOSS, 50/50 OHM
FREQ(HZ)
150K
500K
1M
10M
30M
CM,dB
48
62
65
52
50
DM, dB
46
56
60
60
60
SPECIFICATIONS SUBJECT TO CHANGE