Home
EMI/RFI FILTERS
Products
About Us
Blog
FAQs
Resources
Terms and Conditions
Warranty Information
Installation Instructions
Contact Us
PF210S-16-10
1PH COMMERCIAL/INDUSTRIAL FILTER
DUAL STAGE / CHASSIS MOUNT
SPECIFICATIONS
Max voltage: 0-300VAC
Max current: 16A/Line
Usable frequency: 50/60/400HZ
Operating temp.: -40 To 50C
Leakage current (250V/60HZ): <1mA
Typ. weight, LB(Kg): 0.45(0.2)
Climatic class: 25/100/21
Designed and manufactured in accordance with the following standards:
EN60939-3
CSA22.2 NO. 8
LV Directive
DOWNLOAD SHEET
TYPICAL INSERTION LOSS, 50/50 OHM
FREQ(HZ)
150K
500K
1M
10M
30M
CM,dB
50
54
60
55
46
DM, dB
32
40
55
60
60
SPECIFICATIONS SUBJECT TO CHANGE