PF407S-100-100
3PH WYE COMMERCIAL/INDUSTRIAL FILTER
SINGLE STAGE / CHASSIS MOUNT
SPECIFICATIONS
Max voltage: 0-520VAC
Max current: 100A/Line
Usable frequency: 50/60/400HZ
Operating temp.: -40 TO 50C
Leakage current (250V/60HZ): <1mA
Typ. weight, LB(Kg): 8.0(3.6)
Climatic class: 25/100/21
Designed and manufactured in accordance with the following standards:
EN60939-3
CSA22.2 NO. 8
LV Directive
DOWNLOAD SHEET
TYPICAL INSERTION LOSS, 50/50 OHM
FREQ(HZ)
150K
500K
1M
10M
30M
CM,dB
60
70
72
58
52
DM, dB
50
68
72
70
66